JG Series pressure regulating stations for boiler


         
 


 

 


 




  Purpose
    JG Series pressure regulating stations is specially used for gas regulating stations, which includes gas-filtering measures, the regulator, the overpressure / loss pressure off safety shutoff and safety relief.The structure is usually like a tank, and covers small area , beautiful designed , suitable for families and outside installation.

    JGSerie for boiler is designed based on the most common used standards . PS:Inlet PressureP1=0.1-0.4MPa(naturl gas ),P1=0.03-0.1MPa(coal gas );Outlet Pressure P2=5-15Kpa.The user can choose the stations according to different heat value (natule gas and coal gas).

Technical Datas


    Applicable medium:Natural gas ,Manufactured gas
    Inlet Pressure Ranges:P1=0.05-0.4 MPa(Natural gas);
    P1=0.03-0.1 MPa (Manufactured gas)
    Outlet Pressure Ranges:P2=5-15 Kpa
    Pressure Regulator Precisionδ: ≤±5%
    Flowmeter Precision: 1.0grade or 1.5 grade
    Close PressurePb: ≤+10%
    Temperature Capabilitiest: -20°-60°C .

Basic Equipment


    JGSeries Regulator Box mainly include: Inlet/Outlet Valve, gas filter, gas pressure regulator,safety shutoff valve, measurement meters, safety relief valve, pipeline and local meters


Flow Chart

 
1.Inlet insulative tie-in(extra)
2.Inlet valve
3.filter 4.Pressure loss gauge(extra)
5.Valve for pressure loss gauge (extra)
6.Inlet Pressure gauge
7. Slam shut valve
8. Pressure reducing regulator
9.Outlet Pressure gauge
10.Outlet valve
11. Passby inlet valve
12.Manual regulator valve(extra)
13. Relief valve
14.Ball valve
15. Outlet insulative tie-in(extra)
16. Meter
17. Ball valve

Process chart is based on the above-mentioned most often used in transmission and distribution process, only can be considered as references, more is based on the user's specific requirements and the related matching Equipments.

Reference Table

No.

MODEL

Inlet Pressure

(MPa)

Outlet Pressure

(KPa)

Rating Flow

(Nm3/h)

Boiler range(T)

Natual Gas

Coal Gas

1

JG100**

0.03-0.4

1-15

100

0.5T,1T

0.5T

2

JG200**

0.03-0.4

5-15

200

1.5T,2T or Total2T boilers

1T

3

JG400**

0.03-0.4

5-15

400

2.5T,3T,4T or Total4T boilers

1.5T,2T or Total2T boilers

4

JG600**

0.03-0.4

5-15

600

5T,6T,8T or total8T and single1T boilers

2.5T,3T,4T or Total4T boilers

5

JG1000**

0.03-0.4

5-15

1000

10T,15T or total15 T and single2T boilers

5T,6T or total8T and single1T boilers

6

JG2000**

0.03-0.4

5-15

2000

20T,25T or total25T and single3T boilers

8T,10T or total10T and single2T boilers

7

JG3000**

0.03-0.4

5-15

3000

30T or total30T and single4T boilers

15T or total15 T and single3T boilers

The rating flow in table :Inlet Pressure 0.1-0.15MPa,under the standard state with 0.61 relative density;The coefficients about coal gas is 1.17.The user can choose our product according to Inlet pressure、Outlet Pressure、Medium、gas heat value and so on .