JG Series pressure regulating stations for boiler
|
|
|
|
|
|
|
|
Purpose
JG Series pressure regulating stations is specially used for gas regulating stations, which includes gas-filtering measures, the regulator, the overpressure / loss pressure off safety shutoff and safety relief.The structure is usually like a tank, and covers small area , beautiful designed , suitable for families and outside installation.
JGSerie for boiler is designed based on the most common used standards . PS:Inlet PressureP1=0.1-0.4MPa(naturl gas ),P1=0.03-0.1MPa(coal gas );Outlet Pressure P2=5-15Kpa.The user can choose the stations according to different heat value (natule gas and coal gas).
Technical Datas
Applicable medium:Natural gas ,Manufactured gas
Inlet Pressure Ranges:P1=0.05-0.4 MPa(Natural gas);
P1=0.03-0.1 MPa (Manufactured gas)
Outlet Pressure Ranges:P2=5-15 Kpa
Pressure Regulator Precisionδ: ≤±5%
Flowmeter Precision: 1.0grade or 1.5 grade
Close PressurePb: ≤+10%
Temperature Capabilitiest: -20°-60°C
.
Basic Equipment
JGSeries Regulator Box mainly include: Inlet/Outlet Valve, gas filter, gas pressure regulator,safety shutoff valve, measurement meters, safety relief valve, pipeline and local meters
Flow Chart
|
|
1.Inlet insulative tie-in(extra)
2.Inlet valve
3.filter
4.Pressure loss gauge(extra)
5.Valve for pressure loss gauge (extra)
6.Inlet Pressure gauge |
7. Slam shut valve
8. Pressure reducing regulator
9.Outlet Pressure gauge
10.Outlet valve
11. Passby inlet valve
12.Manual regulator valve(extra) |
13. Relief valve
14.Ball valve
15. Outlet insulative tie-in(extra)
16. Meter
17. Ball valve |
Process chart is based on the above-mentioned most often used in transmission and distribution process, only can be considered as references, more is based on the user's specific requirements and the related matching Equipments.
Reference Table
No. |
|
Inlet Pressure
(MPa) |
Outlet Pressure
(KPa) |
Rating Flow
(Nm3/h) |
Boiler range(T) |
Natual Gas |
Coal Gas |
1 |
JG-100** |
0.03-0.4 |
1-15 |
|
0.5T,1T |
0.5T |
2 |
JG-200** |
0.03-0.4 |
5-15 |
200 |
1.5T,2T or Total≤2T boilers |
1T |
3 |
JG-400** |
0.03-0.4 |
5-15 |
400 |
2.5T,3T,4T or Total≤4T boilers |
1.5T,2T or Total≤2T boilers |
4 |
JG-600** |
0.03-0.4 |
5-15 |
600 |
5T,6T,8T
or total≤8T and single≥1T boilers |
2.5T,3T,4T or Total≤4T boilers |
5 |
JG-1000** |
0.03-0.4 |
5-15 |
1000 |
10T,15T or total≤15
T and single≥2T boilers |
5T,6T or total≤8T
and single≥1T boilers |
6 |
JG-2000** |
0.03-0.4 |
5-15 |
2000 |
20T,25T or total≤25T
and single≥3T boilers |
8T,10T or total≤10T
and single≥2T boilers |
7 |
JG-3000** |
0.03-0.4 |
5-15 |
3000 |
30T or
total≤30T and single≥4T boilers |
15T or
total≤15 T and single≥3T boilers |
The rating flow in table :Inlet Pressure 0.1-0.15MPa,under the standard state with 0.61 relative density;The coefficients about coal gas is 1.17.The user can choose our product according to Inlet pressure、Outlet Pressure、Medium、gas heat value and so on .
|
|
|
|
|
|
|